Product overview
XZ2-SPD80、100、150、200 series surge protector is suitable for low-voltage AC power distribution 50/60Hz, 230/4oov and below IT, TT, TN-C, TN-S, TN-C-S and other power supply systems can be connected in parallel on the power line for equal potential when lightning strikes. Mainly used to protect low-voltage customer electrical installations from surges caused by atmospheric discharge (e.g. to indirect lightning) or other operating instantaneous overvoltages. As a single voltage limiting device. Products in line with GB18802.1, GB50057 and lEC/EN61643-11 standards.
The SPD has a built-in disconnector. When the SPD fails due to overheating or breakdown, the disconnector can automatically disconnect it from the power grid and give an indication signal. The visual window displays green when SPD is working normally, and red when it disengages.
The protection device shall be installed at the end of the upline (immediately connected to the downline of the pull-in wire) required to protect the customer's equipment, connecting the outer lead (L) or neutral lead (N) to the grounding device of the customer's equipment. It is installed at the junction of LPZOA zone and LPZ1 zone, with 35mm standard guide rail and 16-35mm2 copper multi-wire connection.
Each front pole of SPD surge protector must be connected in series with XZSCB series surge backup protector or fuse.
Usually installed in the line of low voltage main distribution cabinet, used for primary power equipment protection, often used in vulnerable to lightning outdoor power distribution cabinets, power distribution cabinets and indoor irfpa have to qualify the roof of the power distribution equipment, suitable for civil construction, electrical, communications, road traffic, such as the petrochemical industry of power equipment protection.
Main technical parameters
Specifications | XZ2-SPD80 | XZ2-SPD100 | XZ2-SPD150 | XZ2-SPD200 | ||||
The number of | 1P、1P+N、2P、3P、3P+N、4P | |||||||
In(8/20 μs) Nominal discharge current |
40kA | 60kA | 80kA | 100kA | ||||
1peak(10/350 μs) The peak current |
80kA | 100kA | 150kA | 200kA | ||||
Uc(VAC) Maximum Continuous Operating Voltage |
385 | 420 | 385 | 420 | 385 | 420 | 385 | 420 |
Uc(kV) Voltage protection level |
2.1 | 2.5 | 2.3 | 2.8 | 2.7 | 3 | 3.2 | 3.5 |
(ns)Response time | <25 | |||||||
Protection grade | IP20 | |||||||
The failure indicator | Green is nomal, red is ineffective | |||||||
Test classification | Class ii | |||||||
Ambient limit femperature TU | -40℃~80℃ | |||||||
Front over current protection device | XZSCB-80 | XZSCB-100 | XZSCB-150 | XZSCB-200 | ||||
Type of installation | 35mm standard guide rail is used for installation | |||||||
(mm2) lnduced power line cross-sectional area |
25-35mm2/ Multicore flexible cable | |||||||
Note | Remote signal function can be added, other maximum continuous working voltage uC can be customized |
Overall dimensions
> The purpose, working principle, and usage instructions of the distribution box
The distribution box is an electrical equipment with the characteristics of small size, easy installation, special technical performance, fixed position, unique conf...
> what does mccb stand for electrical
MCCB stands for Molded Case Circuit Breaker, which is a type of electrical circuit breaker that is used to protect electrical circuits from overloads and short circu...
> MCCB and ACB Difference
MCCBs are suitable for small applications with lower current ratings, while ACBs are more suitable for larger applications with higher current ratings and higher fau...
> What is the working principle of a timer
Timer is an instrument used to control time. With the advancement of science and technology, people have continuously improved and upgraded timers, and now they can ...